Portable Fire Extinguisher Service
Fire extinguishers are the essential weapon for first-strike combat of any type of fire. As such, they must always be pressurized and full. A partially charged, or neglected extinguisher may not be reliable in a fire situation. All occupancies covered by the National Fire Code require monthly and annual inspections of portable extinguishers. Any dry chemical extinguisher, whether for private or commercial use, should be disassembled, inspected internally and re-built every 6 years and hydrostatically tested every 12 years. Extinguishers containing other agents are subject to other periodic maintenance. The Fire Code dictates that only certified agencies may perform inspections and service. Atlas Fire & Safety Equipment Ltd. is a Warnock Hersey listed fire extinguisher service agency and strictly adheres to required practices
Fire Extinguisher Hydrostatic Testing
In accordance with the Canadian Transport Commissions (CTC)
requirements, hydrostatic testing is required to test a cylinders integrity
prior to continued service life. This is performed by filling the cylinder
with water and pressurizing it while inside a safety cage or water jacket.
A hydrostatic test is required by code every 5 years for Pressurized
Water, CO2, and K-Type extinguishers, and every 12 years for Dry Chemical
extinguishers.
|
 |
|
 |